Project Overview

Sub Soil Investigation was successfully completed by Geo Builders for a proposed G+09 residential building at Dakshinkhan, Dhaka. Three boreholes were drilled and detailed field and laboratory investigations were carried out to evaluate the engineering properties of the subsoil. Standard Penetration Test (SPT), soil classification, shear strength, consolidation and other laboratory analyses were performed in accordance with BNBC, ASTM, AASHTO, BS and IS standards. Based on the investigation results, a pile foundation system was recommended to ensure structural safety, adequate bearing capacity and long-term performance of the proposed building.

Pile Foundation is recommended as the most economical and structurally safe foundation system for the proposed G+09 (10 Storied) residential building. Recommended pile capacities: Pile Diameter 75 ft 80 ft 18" 62.12 Ton 71.54 Ton 20" 73.24 Ton 84.48 Ton 24" 97.22 Ton 112.40 Ton

Lab Tests Equipment Used & Followed Standards

Rotary Drilling Rig Tripod Split Spoon Shelby Tube SPT Hammer

Soil Test Summary (Sample)

Depth (ft)Soil TypeSPT N-ValueRemarks
0 - 5Fill / Loose Soil5 - 8Low bearing
5 - 20Silty Clay8 - 15Medium dense
20 - 40Sandy Silt15 - 25Suitable
40 - 90Dense Sand25 - 40Good bearing

Project Location

Recommendation : Pile Foundation is recommended as the most economical and structurally safe foundation system for the proposed G+09 (10 Storied) residential building. Recommended pile capacities: Pile Diameter 75 ft 80 ft 18" 62.12 Ton 71.54 Ton 20" 73.24 Ton 84.48 Ton 24" 97.22 Ton 112.40 Ton